Safety and commissioning information for Ex areas 
  14.2 Dry-running protection for centrifugal pumps by active power monitoring 
SIMOCODE pro 
System Manual, 05/2019, A5E40507475002A/RS-AD/004 
321 
 
Note 
Log file 
For verification purposes, we recommend generating a log file (see Chapter "Dry
-running 
protection of centrifugal pumps" in the manual Parameterizing SIMOCODE p
ro 
https://support.industry.siemens.com/cs/ww/en/view/109743958)) after setting the 
parameters (whether done as a teach
-in or by means of direct entry using SIMOCODE ES). 
 
Note 
Activating the dry-running protection function 
This function i
s deactivated in the as-delivered state. 
The function is activated following a successful run
-
through with the wizard. The response of 
the dry
-running protection at P
TRIP
 < (lower threshold) is set to "Trip". 
 
Note 
Default setting for response 
The respo
nse of the dry-running protection at P
TRIP
 < (lower threshold) is preset to "Trip". 
 
Note 
Setting the warning level 
You have the option of configuring an additional warning level for undershooting of active 
power using the "Active power monitoring" func
tion (see Chapter "Active power monitoring" 
in the manual Parameterizing SIMOCODE pro 
(
https://support.industry.siemens.com/cs/ww/en/view/109743958)). This becomes effective 
fore the trip level P
TRIP
 is undershot. 
However, this warning level is of no relevance with respect to approval for use 
in hazardous 
 
 
Manufacturer's instructions on the centrifugal pump 
Observe the manufacturer's instructions for the centrifugal pump, which must be protected 
against dry running, in particular the characteristic curve which supplies the information on 
the minimum flow rate and possible information for the procedure during startup and 
shutdown of the pump / motor.