Technical data   
15.4 Technical data of the current measuring modules and the current / voltage measuring modules 
  SIMOCODE pro 
344  System Manual, 05/2019, A5E40507475002A/RS-AD/004 
Technical data of the current measuring modules or the 1st generation current / voltage measuring modules 
Connection for voltage measurement 
•  Tightening torque 
TORQUE: 7 lb.in - 10.3 lb.in 
•  Connection cross sections 
 
 - Solid  1 x 0.5 mm
2
 - 4 mm
2
 / 1 x AWG 20 to 12 
2
2
 - Finely stranded with end sleeve  1 x 0.5 mm
2
 - 2.5 mm
2
 / 1 x AWG 20 to 14 
2
2
1) for 3UF7103 or 3UF7104 to 1000 V 
2) for 3UF7103 or 3UF7104 to 8 kV 
3) You will find more information at SIMOCODE pro (https://www.siemens.com/simocode) and in Chapter 
Short-circuit 
protection with fuses for motor feeders for short-circuit currents up to 100 kA and 690 V for 1st generation current / voltage 
measuring module
 (Page 364) 
4) Screw connection is possible with an appropriate 3RT19 box terminal. 
5) When connecting cable lugs complying with DIN 46235 to cables with a cross section larger than 95 mm
2
, the 
3RT19 56-4EA1 terminal cover is required to maintain phase separation. 
6) When connecting cable lugs complying with DIN 46234 to cables with a cross section larger than 240 mm
2
 and when 
connecting cable lugs complying with DIN 46235 to cables with a cross section larger than 185 mm
2
, the 3RT19 56-4EA1 
terminal cover is required to maintain phase separation. 
7) Valid for float values 
8) A current range of 0.4 - 8 A is necessary for the 3UF7110-1AA01-0 version