Overview of functions   
5.8 Operating, service and diagnostics data 
  SIMOCODE pro 
60  System Manual, 05/2019, A5E40507475002A/RS-AD/004 
Service data 
Among other things, SIMOCODE pro provides the following relevant data for maintenance: 
●  Number of motor operating hours, also resettable 
●  Motor stop times, also resettable 
●  Number of motor starts, also resettable 
●  Number of permissible starts remaining 
●  Number of overload trips, also resettable 
●  Feeder power consumption in kWh, also resettable
 2)
 
●  Internal feeder-related comments stored in the device, e.g. information regarding 
maintenance events, etc. 
●  Safety-related tripping monitoring in h, also resettable
 5)
 
Diagnostics data 
●  Numerous detailed early warning and fault messages, also for further processing in the 
device or in the control system 
●  Device-internal error logging with time stamp 
●  Value of the last trip current 
●  Feedback faults (e.g. no current flow in the main circuit after switch-on command), etc. 
●  "Local" and "PROFIsafe" diagnostic messages 
 
1) When using SIMOCODE pro V High Performance basic units with current / voltage 
measuring module 
2) When using SIMOCODE pro V PB basic units from version *E03* current / voltage 
measuring module 
3) When using the SIMOCODE pro V basic units with the 3UF77 temperature module or the 
SIMOCODE pro S basic unit with multifunction module 
4) When using SIMOCODE pro V High Performance basic units with analog module 
5) When using SIMOCODE pro V High Performance basic units together with DM-F fail-safe 
digital module 
6) When using the SIMOCODE pro V basic units with the 3UF7510 ground-fault module or 
the SIMOCODE pro S basic unit with a multifunction module and 3UL23 residual current 
transformer 
7) 2nd generation current / voltage measuring module necessary