4. Reconnect the Hall sensor at X300.
5. Reconnect the encoder connecting cable.
6. Connect the DRIVE-CLiQ cable.
Note
Connections/cables
The maximum DRIVE-CLiQ cable length is 100 m.
The maximum encoder cable length is 3 m.
In order to guarantee the degree of protection, all of the plug connectors must be correctly
screwed and snapped into place.
4.17.7 SME125 connections
Connections
Requirements: The control cabinet is in a no-voltage condition, all of the connectors and cables
are labeled.
3URWHFWLYHFRQGXFWRU
FRQQHFWLRQ
01PPPt
;
;
;
X100 Encoder system interfaces, tightening torque: 3.5 Nm
X200 Temperature sensor input, tightening torque: 2 Nm
X500 DRIVE-CLiQ
Figure 4-61 SME125 connections
4.17.8 This is how you remove an SME125 and install it again
Removing
Procedure:
1. Release the encoder connecting cable X100 of the SME125
2. Withdraw the DRIVE-CLiQ cable from X500 of the SME125.
Service cases - hardware
4.17 Sensor Modules External
Software and hardware
218 Service Manual, 08/2018, 6FC5397-5DP40-6BA1