06.03
2.13 ADI4 (analog drive interface for 4 axes) (SW 09.01 and higher)
2-120
Siemens AG, 2003. All rights reserved
SINUMERIK 840Di Manual (HBI) – 06.03 Edition
The external power supplies for the ADI4 module, the digital outputs, and op-
tionally the digital inputs must meet the specifications in Table 2-30.
Table 2-37 Specification of the external power supplies
Supply voltage
1)
P24EXT1 P24EXT2 P24OUText
Voltage
minimum 18.5V
nominal 24V
max. 30.2V
Ripple
max. 3.6Vpp
Current load
typical 0.5A 0.1A
max. 1A 8A 1A
Power consumption
typical 12W 3.02W
max. 30.2W 241.6W 30.2W
1) P24EXT1: Supply voltage of the ADI4 module
P24EXT2: Supply voltage for the digital outputs
P24OUText: Optional supply voltage for the digital inputs
Caution
The external power supply voltages must be generated as functional extra-low
voltages with safe electrical isolation (DIN EN 60204-1, Section 6.4, PELV).
On the module side, power supplies P24EXT1 and P24EXT2 must be protected
against:
S Overvoltage
S Short-circuit (elec. current limitation of the outputs)
S Polarity reversal
S Overload
P24EXT1: Fuse 2.5A/250V
P24EXT2: Fuse 8A/125V.
Specification of
the power supplies
(+24VDC)