Plug-In Module
USART-AB-1EL
USART-AC-2EL
USART-AD-1FO
USART-AE-2FO
ETH-BA-2EL
ETH-BB-2FO
ETH-BD-2FO
1
ETH-YA-2FO
USART-AF-1LDFO
USART-AW-2LDFO
USART-AG-1LDFO
USART-AU-2LDFO
USART-AK-1LDFO
USART-AV-2LDFO
USART-AH-1LDFO
2
USART-AJ-1LDFO
3
USART-AX-2LDFO
4
USART-AY-2LDFO
5
ANAI-CA-4EL
ARC-CD-3FO
SUP Ethernet (Slave Unit Protocol) for
connecting external temperature or
20-mA measuring devices
Diagnosis: Ethernet module homepage
(http)
Measuring transducer, 4 inputs, DC
±20 mA
Arc protection
Additional Ethernet protocols and services
DHCP, DCP (automatic IP configuration)
Line Mode
PRP (Ethernet ring redundancy)
HSR (Ethernet ring redundancy)
8
RSTP (Ethernet ring redundancy)
SNTP (time synchronization via
Ethernet)
SNMP V3 (network management
protocol)
9
IEEE 1588v2 (PTP protocol via Ethernet
– ms accuracy)
IEEE 1588v2 (PTP protocol via Ethernet
– µs accuracy)
10
IEEE 802.1q (VLAN)
i
i
NOTE
The USART and ETH plug-in module types can be used in slots E and F in the base module as well as in slots
N and P in the CB202 expansion module. They are not intended for use in slot M in the CB202 expansion
module.
The plug-in modules of types ANAI and ARC can be used in both slots in the base module (ports E and F), as
well as in all slots in the expansion module CB202 (ports M, N, and P).
i
i
NOTE
For SIPROTEC 5 Compact devices, only the fixed modules ETH-YC-2EL
11
and ETH-YA-2FO are available.
The modules ETH-YC-2EL and ETH-YA-2FO are not available for SIPROTEC 5 devices.
1
For modular devices only (not for 7ST85 and 6MD89)
2
USART-AH-1LDFO only in connection with USART-AJ-1LDFO or USART-AY-2LDFO
3
USART-AJ-1LDFO only in connection with USART-AH-1LDFO or USART-AX-2LDFO
4
USART-AX-2LDFO only in connection with USART-AJ-1LDFO or USART-AY-2LDFO
5
USART-AY-2LDFO only in connection with USART-AH-1LDFO or USART-AX-2LDFO
8
HSR is available in the ETH-BD-2FO module for V8.30 and higher. The IEEE 1588v2 Transparent Clock is supported for V8.80 and
higher.
9
Available for V8.30 and higher.
10
SFP accuracy is 1 ms with optional RJ45
11
In preparation
Plug-In Modules
4.2 Communication Modules
SIPROTEC 5, Hardware Description, Manual 161