Page #214 background imageLoading...
Page #214 background image
i
i
NOTE
You can read the type of the current transformer used on the side of the terminal block, for example 3xI
1xIE. The reference number is located on the connector interface and can only be read when removed.
C73334A 1A1*7 * = 4 protection-class current transformers
C73334A 1A1*8 * = 3 protection-class current transformers and 1 instrument transformer
C73334A 1A1*9 * = 4 instrument transformers
Current-Terminal Block for Non-Modular Devices (7xx81, 7xx82)
The following transformers can be installed optionally in a current-terminal block for non-modular devices:
4 protection-class current transformers
3 protection-class current transformers and 1 instrument transformer
Protection-class current transformers on non-modular devices are transformers with a rated current of 1 A or
5 A and a measuring range of 50 x rated current.
Instrument transformers are transformers with a rated current of 1 A or 5 A and a measuring range of
1.6 x rated current. Instrument transformers are also referred to as sensitive protection-class current trans-
formers or sensitive ground-current transformers.
i
i
NOTE
You can read the type of the current transformer used on the side of the terminal block, for example 3xI
1xIE. The reference number is located on the connector interface and can only be read when removed.
C73334A 1A185 * = 4 protection-class current transformers
C73334A 1A186 * = 3 protection-class current transformers and 1 instrument transformer
Use the cross connector for voltage terminals shown on the right in the following figure for grouping binary
inputs and relay outputs.
[dwquerve-030211-01.tif, 1, --_--]
Figure 5-25 Cross Connector for Current (Left) and Voltage Terminals (Right)
[dwkappst-030211-01.tif, 1, --_--]
Figure 5-26 Covering Cap for Current-Terminal Block
Working on the Device
5.7 Installing Current and Voltage Terminals
214 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-M, Edition 12.2021

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 V8.83 and is the answer not in the manual?

Siemens SIPROTEC 5 V8.83 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 5 V8.83
CategoryPower distribution unit
LanguageEnglish

Related product manuals