2 Functions
308
7SA522 Manual
C53000-G1176-C155-3
End Fault Protec-
tion     
An end fault is defined here as a short–circuit which has occurred at the end of a line 
or protected object, between the circuit breaker and the current transformer set.
This situation is shown in Figure 2-133. The fault is located — as seen from the current 
transformers (= measurement location) — on the bus-bar side, thus, it will not be re-
garded by the feeder protection relay as a feeder fault. It can only be detected by either 
a reverse stage of the feeder protection or by a busbar protection. Nevertheless, a trip 
command given to the feeder circuit breaker cannot clear the fault since the opposite 
end continues to feed the fault. Thus, the fault current does not stop flowing even 
though the feeder circuit breaker has properly responded to the trip command.
Figure 2-133 End fault between circuit breaker and current transformers
The end fault protection has the task to recognize this situation and to transmit a trip 
signal to the remote end(s) of the protected object to clear the fault. For this purpose, 
the output command ´%)(QG)OW75,3µ is available to trigger a signal transmission 
device (e.g. power line carrier, radio wave, or optical fibre) — if applicable, together 
with other commands that need to be transferred or (when using digital signal trans-
mission) as command via the protection interface.
The end fault is recognized when the current continues flowing although the circuit 
breaker auxiliary contacts indicate that the breaker is open. An additional criterion is 
the presence of any breaker failure protection initiate signal. Figure 2-134 illustrates 
the functional principle. If the breaker failure protection is initiated and current flow is 
detected (current criteria “L*>” according to Figure 2-122), but no circuit breaker pole 
is closed (auxiliary contact criterion “ ≥ any pole closed”), then the timer 7(QG)DXOW 
is started. At the end of this time an intertrip signal is transmitted to the opposite end(s) 
of the protected object.
Figure 2-134 Operation scheme of end fault protection
Pole Discrepancy 
Supervision 
The pole discrepancy supervision has the task to detect discrepancies in the position 
of the three circuit breaker poles. Under steady-state operating conditions, either all 
three poles of the breaker must be closed, or all three poles must be open. Discrep-