2 Functions
332
7SA522 Manual
C53000-G1176-C155-3
&ORVHµ must be triggered by a separate contact at the control discrepancy switch
(Figure 2-149).
If in that latter case a manual close command can also be given by means of an inter-
nal control command from the device, such a command must be combined with the
manual CLOSE function via parameter  0DQ&ORV,PS (Figure 2-147).
Figure 2-149 Manual closing with external automatic reclosure device
Besides the manual CLOSE detection the device records any energization of the line
via the integrated line energization detection. This function processes a change-of-
state of the measured quantities as well as the position of the breaker auxiliary con-
tacts. The current status of the circuit breaker is detected, as described in the following
Section at “Detection of the Circuit Breaker Position”. The criteria for the line energi-
zation detection change according to the local conditions of the measuring points and
the setting of the parameter address  /LQH&ORVXUH (see Section 2.1.5 at
margin heading “Circuit Breaker Status”).
The phase-phase currents and the phase-earth voltages are available as measuring
quantities. A flowing current excludes that the circuit breaker is open (exception: a
fault between current transformer and circuit breaker). If the circuit breaker is closed,
it may however still occur that no current is flowing. The voltages can only be used as
a criterion for the de-energized line if the voltage transformers are installed on the
feeder side. Therefore, the device only evaluates those measuring quantities that
provide information on the status of the line according to address .
But a change-of-state, such as a voltage jump from zero to a considerable value (ad-
dress  3ROH2SHQ9ROWDJH) or the occurrence of a considerable current (ad-
dress  3ROH2SHQ&XUUHQW) without a line voltage appearing at the same time,
can be a reliable indicator for line energization as such changes can neither occur
during normal operation nor in case of a fault.
The position of the auxiliary contacts of the circuit breakers indicate directly the posi-
tion of the circuit breaker. If the circuit breaker is controlled single-pole, the critierion
for energization is if at least one contact changes from open to closed.
The detected energization is signaled through the message ´/LQHFORVXUHµ (FNo
590). In order to be independent of the duration that the switch is closed, the signal is
set to a defined length in the device (adjustable with the address  6,7LPHDOO
&O). Figure 2-150 shows the logic diagram.

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals