3.1 Mounting and Connections
381
7SA522 Manual
C53000-G1176-C155-3
Table 3-2 Jumper settings of the nominal voltage of the integrated Power Supply of the
input/output module C-I/O-1.
Table 3-3 Jumper position of the quiescent state of the Life contact on the C-I/O-1 in-
put/output module
Depending on the device version the contacts of some binary outputs can be changed
from from normally open to normally closed (see Appendix, under section A.2).
In versions 7SA522*-*D/H/M (housing size
1
/
1
with 32 binary outputs) this is valid
for the binary outputs BO16 and BO24 (Figure 3-4, slot 19 left and right);
In versions 7SA522*-*C/G/L (housing size
1
/
1
with 24 binary outputs) this is valid for
the binary output BO16 (Figure 3-4, slot 19 right);
In versions 7SA522*-*P/R/T (housing size
1
/
1
with 32 binary outputs and command
acceleration) this is valid for the binary output BO24 (Figure 3-4, slot 19 left).
Table 3-4 shows the jumper settings for the contact mode.
Table 3-4 Jumper settings for contact mode of the relays for BO B16 and BO24 on the
C–I/O-1 input/output board
Jumper
Nominal Voltage
60/110/125 VDC 110/125/220/250 VDC 115 VAC 24/48 VDC
X51 1-2 2-3 Jumpers X51 to
X53 are not used
X52 1-2 and 3-4 2-3
X53 1-2 2-3
interchangeable cannot be
changed
Jumper
Open in quiescent state
(NO)
Closed in quiescent state
(NC)
Presetting
X40 1-2 2-3 2-3
Relay
7SA522*–*
Module for Jumper Open in quies-
cent state (NO)
Closed in quiescent state
(NC)
Presetting
D/H/M Slot 19 left side BO 16 X40 1-2 2-3 1-2
Slot 19 right
side
BO 24 X40 1-2 2-3 1-2
C/G/L Slot 19 right
side
BO 16 X40 1-2 2-3 1-2
P/R/T Slot 19 left side BO 24 X40 1-2 2-3 1-2