A Appendix
554
7SA522 Manual
C53000-G1176-C155-3
515 Relay TRIP command Phases
L123 (Relay TRIP 3ph.)
P.System Data 2 OUT * * * LED BO
530 LOCKOUT is active (LOCKOUT) P.System Data 2 IntSP ON
OFF
ON
OFF
* LED BO 150 170 1 Yes
533 Primary fault current IL1 (IL1 =) P.System Data 2 OUT * ON
OFF
150 177 4 No
534 Primary fault current IL2 (IL2 =) P.System Data 2 OUT * ON
OFF
150 178 4 No
535 Primary fault current IL3 (IL3 =) P.System Data 2 OUT * ON
OFF
150 179 4 No
536 Relay Definitive TRIP (Definitive
TRIP)
P.System Data 2 OUT ON ON * * LED BO 150 180 2 No
545 Time from Pickup to drop out (PU
Time)
P.System Data 2 OUT
546 Time from Pickup to TRIP (TRIP
Time)
P.System Data 2 OUT
560 Single-phase trip was coupled
3phase (Trip Coupled 3p)
P.System Data 2 OUT * ON * LED BO 150 210 2 No
561 Manual close signal detected
(Man.Clos.Detect)
P.System Data 2 OUT ON * * LED BO 150 211 1 No
562 CB CLOSE command for manual
closing (Man.Close Cmd)
P.System Data 2 OUT * * * LED BO 150 212 1 No
563 CB alarm suppressed (CB Alarm
Supp)
P.System Data 2 OUT * * * LED BO
590 Line closure detected (Line clo-
sure)
P.System Data 2 OUT ON
OFF
ON
OFF
mLED BO
591 Single pole open detected in L1
(1pole open L1)
P.System Data 2 OUT ON
OFF
ON
OFF
mLED BO
592 Single pole open detected in L2
(1pole open L2)
P.System Data 2 OUT ON
OFF
ON
OFF
mLED BO
593 Single pole open detected in L3
(1pole open L3)
P.System Data 2 OUT ON
OFF
ON
OFF
mLED BO
916 Increment of active energy
(Wp=)
Energy -
917 Increment of reactive energy
(Wq=)
Energy -
1000 Number of breaker TRIP com-
mands (# TRIPs=)
Statistics OUT
1001 Number of breaker TRIP com-
mands L1 (TripNo L1=)
Statistics OUT
1002 Number of breaker TRIP com-
mands L2 (TripNo L2=)
Statistics OUT
1003 Number of breaker TRIP com-
mands L3 (TripNo L3=)
Statistics OUT
1027 Accumulation of interrupted
current L1 (Σ IL1 =)
Statistics OUT
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Inputs
Function Key
Relay
Chatter suppression
Type
Information Number
Data Unit
General Interrogation