A.8 Information List
575
7SA522 Manual
C53000-G1176-C155-3
4231 Weak Infeed PICKED UP (Weak-
Inf. PICKUP)
Weak Infeed OUT * OFF * LED BO 25 31 2 Yes
4232 Weak Infeed PICKUP L1 (W/I
Pickup L1)
Weak Infeed OUT * ON * LED BO
4233 Weak Infeed PICKUP L2 (W/I
Pickup L2)
Weak Infeed OUT * ON * LED BO
4234 Weak Infeed PICKUP L3 (W/I
Pickup L3)
Weak Infeed OUT * ON * LED BO
4241 Weak Infeed General TRIP
command (WeakInfeed TRIP)
Weak Infeed OUT * * * LED BO 25 41 2 No
4242 Weak Infeed TRIP command -
Only L1 (Weak TRIP 1p.L1)
Weak Infeed OUT * ON * LED BO 25 42 2 No
4243 Weak Infeed TRIP command -
Only L2 (Weak TRIP 1p.L2)
Weak Infeed OUT * ON * LED BO 25 43 2 No
4244 Weak Infeed TRIP command -
Only L3 (Weak TRIP 1p.L3)
Weak Infeed OUT * ON * LED BO 25 44 2 No
4245 Weak Infeed TRIP command
L123 (Weak TRIP L123)
Weak Infeed OUT * ON * LED BO 25 45 2 No
4246 ECHO Send SIGNAL (ECHO
SIGNAL)
Weak Infeed OUT ON ON * LED BO 25 46 2 Yes
4247 ECHO Tele.Carrier RECEPTION,
Device1 (ECHO Rec. Dev1)
Echo Rec. ov.PI OUT ON
OFF
ON * LED BO
4248 ECHO Tele.Carrier RECEPTION,
Device2 (ECHO Rec. Dev2)
Echo Rec. ov.PI OUT ON
OFF
ON * LED BO
4249 ECHO Tele.Carrier RECEPTION,
Device3 (ECHO Rec. Dev3)
Echo Rec. ov.PI OUT ON
OFF
ON * LED BO
4253 >BLOCK Instantaneous SOTF
Overcurrent (>BLOCK SOTF-
O/C)
SOTF Overcurr. SP * * * LED BI BO
4271 SOTF-O/C is switched OFF
(SOTF-O/C OFF)
SOTF Overcurr. OUT ON
OFF
**LEDBO25711Yes
4272 SOTF-O/C is BLOCKED (SOTF-
O/C BLOCK)
SOTF Overcurr. OUT ON
OFF
ON
OFF
* LED BO 25 72 1 Yes
4273 SOTF-O/C is ACTIVE (SOTF-
O/C ACTIVE)
SOTF Overcurr. OUT * * * LED BO 25 73 1 Yes
4281 SOTF-O/C PICKED UP (SOTF-
O/C PICKUP)
SOTF Overcurr. OUT * OFF * LED BO 25 81 2 Yes
4282 SOTF-O/C Pickup L1 (SOF
O/CpickupL1)
SOTF Overcurr. OUT * ON * LED BO 25 82 2 Yes
4283 SOTF-O/C Pickup L2 (SOF
O/CpickupL2)
SOTF Overcurr. OUT * ON * LED BO 25 83 2 Yes
4284 SOTF-O/C Pickup L3 (SOF
O/CpickupL3)
SOTF Overcurr. OUT * ON * LED BO 25 84 2 Yes
4295 SOTF-O/C TRIP command L123
(SOF O/CtripL123)
SOTF Overcurr. OUT * ON * LED BO 25 95 2 No
4403 >BLOCK Direct Transfer Trip
function (>BLOCK DTT)
DTT Direct Trip SP * * * LED BI BO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Inputs
Function Key
Relay
Chatter suppression
Type
Information Number
Data Unit
General Interrogation