Functions
2.5 Voltage Protection 27, 59
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
109
2.5.5 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr. Parameter Setting Options Default Setting Comments
5001 FCT 59 OFF
ON
Alarm Only
OFF 59 Overvoltage Protection
5002 59-1 PICKUP 20 .. 260 V 110 V 59-1 Pickup
5003 59-1 PICKUP 20 .. 150 V 110 V 59-1 Pickup
5004 59-1 DELAY 0.00 .. 100.00 sec; ∞ 0.50 sec 59-1 Time Delay
5005 59-2 PICKUP 20 .. 260 V 120 V 59-2 Pickup
5006 59-2 PICKUP 20 .. 150 V 120 V 59-2 Pickup
5007 59-2 DELAY 0.00 .. 100.00 sec; ∞ 0.50 sec 59-2 Time Delay
5015 59-1 PICKUP V2 2 .. 150 V 30 V 59-1 Pickup V2
5016 59-2 PICKUP V2 2 .. 150 V 50 V 59-2 Pickup V2
5017A 59-1 DOUT RATIO 0.90 .. 0.99 0.95 59-1 Dropout Ratio
5018A 59-2 DOUT RATIO 0.90 .. 0.99 0.95 59-2 Dropout Ratio
5019 59-1 PICKUP V1 20 .. 150 V 110 V 59-1 Pickup V1
5020 59-2 PICKUP V1 20 .. 150 V 120 V 59-2 Pickup V1
5101 FCT 27 OFF
ON
Alarm Only
OFF 27 Undervoltage Protection
5102 27-1 PICKUP 10 .. 210 V 75 V 27-1 Pickup
5103 27-1 PICKUP 10 .. 120 V 45 V 27-1 Pickup
5106 27-1 DELAY 0.00 .. 100.00 sec; ∞ 1.50 sec 27-1 Time Delay
5110 27-2 PICKUP 10 .. 210 V 70 V 27-2 Pickup
5111 27-2 PICKUP 10 .. 120 V 40 V 27-2 Pickup
5112 27-2 DELAY 0.00 .. 100.00 sec; ∞ 0.50 sec 27-2 Time Delay
5113A 27-1 DOUT RATIO 1.01 .. 3.00 1.20 27-1 Dropout Ratio
5114A 27-2 DOUT RATIO 1.01 .. 3.00 1.20 27-2 Dropout Ratio
5120A CURRENT SUPERV. OFF
ON
ON Current Supervision