Functions
2.16 Phase Rotation
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
238
2.16.2 Setting Notes
Setting the Function Parameter
The normal phase sequence is set at 209 (see Section 2.1.3). If, on the system side, phase rotation is reversed
temporarily, then this is communicated to the protective device using the binary input „>Reverse Rot.“
(5145).