EasyManua.ls Logo

Siemens SIPROTEC 7SK80 - Connections of the Current Terminals

Siemens SIPROTEC 7SK80
490 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
293
3.1.2.2 Connections of the Current Terminals
Fixing Elements
The fixing elements for the transformer connection are part of the current terminal (housing side). They have a
stress-crack- and corrosion-resistant alloy. The head shape of the terminal screw allows for using a flat screw-
driver (5.5 mm x 1.0 mm / 0.20 in x 0.039 in) or a crosstip screwdriver (PZ2). PZ2 is recommended.
Cable Lugs and Wire Cross-sections
There are two connection options: the connection of single wires and the connection with a ring lug. Only
copper wires may be used.
We recommend ring lugs with the following dimensions:
Figure 3-5 Ring lug
For complying with the required insulation clearances, insulated ring lugs have to be used. Otherwise, the crimp
zone has to be insulated with corresponding means (e.g. by pulling a shrink-on sleeve over).
We recommend ring lugs of the PIDG range from Tyco Electronics.
Two ring lugs can be mounted per connection.
Figure 3-6 Current transformer connection

Table of Contents

Related product manuals