Introduction
1.3 Characteristics
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
23
1.3 Characteristics
General Characteristics
Powerful 32-bit microprocessor system.
Complete digital processing and control of measured values, from the sampling of the analog input quanti-
ties to the initiation of outputs, for example, tripping or closing circuit breakers or other switchgear devices.
Total electrical separation between the internal processing stages of the device and the external transformer,
control, and DC supply circuits of the system because of the design of the binary inputs, outputs, and the
DC or AC converters.
Complete set of functions necessary for the proper protection of lines, feeders, motors, and busbars.
Easy device operation through an integrated operator panel or by means of a connected personal computer
running DIGSI.
Continuous calculation and display of measured and metered values on the front of the device.
Storage of min/max measured values (slave pointer function) and storage of long-term mean values.
Recording of event and fault data for the last 8 system faults (fault in a network) with real-time information
as well as instantaneous values for fault recording for a maximum time range of 18 s.
Constant monitoring of the measured quantities, as well as continuous self-diagnostics covering the hard-
ware and software.
Communication with SCADA or substation controller equipment via serial interfaces through the choice of
data cable, modem, or optical fibers.
Battery-buffered clock which can be synchronized via a synchronization signal at the binary input or via a
protocol.
Switching statistics: Recording of the number of trip signals initiated by the device and logging of currents
switched off last by the device, as well as accumulated short circuit currents of each pole of the circuit break-
er.
Motor Statistics: Recording of the operational information and startup information such as the total number
of motor starts, motor operating hours, percentage of motor operating time, total megawatt hours, and the
startup information duration and currents for each motor startup.
Operating Hours Counter: Tracking of operating hours of the equipment being protected.
Commissioning aids such as connection and direction check, status indication of all binary inputs and out-
puts, easy testing of port B and influencing of information at port B during test operation.
Time Overcurrent Protection 50, 51, 50N, 51N
Three definite time overcurrent protective Elements and one inverse time overcurrent protective element for
phase current and ground current I
N
or summation current 3I
0
;
Allowence of a two-phase (I
A
, I
C
) time overcurrent protection;
For inverse time overcurrent protection, selection from various characteristics of different standards possi-
ble.
Blocking capability e.g. for reverse interlocking with any Element;
Instantaneous tripping by any overcurrent Element upon switch onto fault is possible;
In-rush restraint with second harmonic current quantities.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SK80 and is the answer not in the manual?

Siemens SIPROTEC 7SK80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SK80
CategoryProtection Device
LanguageEnglish

Related product manuals