Introduction
1.3 Characteristics
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
24
Ground Fault Protection 50N, 51N
• Three definite time overcurrent protective Elements and one inverse time overcurrent protective element ap-
plicable for grounded or high-resistance grounded systems;
• For inverse time overcurrent protection, selection from various characteristics of different standards.
• In-rush restraint with second harmonic current quantities;
• Instantaneous tripping by any overcurrent Element during switch onto fault is possible;
Dynamic Cold Load Pick-up Function 50C, 50NC, 51C, 51NC, 67C, 67NC
• Dynamic changeover of time overcurrent protection settings, e.g. when cold load conditions are recognized;
• Detection of cold load condition via circuit breaker position or current threshold;
• Activation also possible via binary input.
Voltage Protection 27, 59
• Two-element undervoltage detection via system positive sequence voltages, phase-to-phase or phase-
ground voltages;
• Choice of current supervision for 27-1 and 27-2;
• Separate two-element overvoltage detection of the largest voltages applied or detection of the positive or
negative sequence component of the voltages.
• settable dropout ratio for all elements of the undervoltage and overvoltage protection.
Negative Sequence Protection 46
• Evaluation of negative sequence component of the currents;
• Two definite-time elements 46-1 and 46-2 and one inverse-time element 46-TOC; curves of common stan-
dards are available for 46-TOC.
Motor Starting Protection 48
• Inverse time tripping Curve based on an evaluation of the motor starting current;
• Definite time delay for blocked rotor.
Motor Restart Inhibit 66, 86
• Approximate replica of excessive rotor temperature;
• Startup is permitted only if the rotor has sufficient thermal reserves for a complete startup;
• Disabling of the start inhibit is possible if an emergency startup is required.
Load Step Function
• Detection of mechanical or thermal overload of the rotor.