Introduction
1.3 Characteristics
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
25
Frequency Protection 81 O/U
Monitoring on underfrequency (f<) and/or overfrequency (f>) with 4 frequency limits and delay times that are
independently adjustable;
Insensitive to harmonics and abrupt phase angle changes;
Adjustable undervoltage threshold.
Thermal Overload Protection 49
Thermal profile of energy losses (overload protection has total memory capability);
True r.m.s. calculation;
Adjustable thermal alarm level;
Adjustable alarm level based on current magnitude;
Additional time constant setting for motors to accommodate the motor at standstill;
Integration of the ambient temperature or coolant temperature is possible via internal temperature detection
or an external thermobox.
Monitoring Functions
Reliability of the device is greatly increased because of self-monitoring of the internal measurement circuits
as well as the hardware and software.
Fuse failure monitor with protection function blocking.
Monitoring of the current transformer and voltage transformer secondary circuits using summation and sym-
metry monitoring with optional protection function blocking.
Trip circuit monitoring;
Phase rotation check.
Ground Fault Detection 50N(s), 51N(s), 67N(s), 59N/64
Displacement voltage is measured or calculated from the three phase voltages;
Determination of a faulty phase on ungrounded or grounded systems;
Two-element Ground Fault Detection: High-set element 50Ns-2 and overcurrent element 50Ns-1.
High sensitivity (as low as 1 mA);
Overcurrent element with definite time or inverse time delay;
For inverse time overcurrent protection, a user-defined characteristic is available.
Direction determination with zero sequence quantities(I
0
, V
0
), wattmetric ground fault direction determina-
tion;
A sector characteristics can be set as directional characteristic.
Any Element can be set as directional or non-directional — forward sensing directional, or reverse sensing
directional;
Optionally applicable as additional ground fault protection.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SK80 and is the answer not in the manual?

Siemens SIPROTEC 7SK80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SK80
CategoryProtection Device
LanguageEnglish

Related product manuals