Functions
2.13 Flexible Protection Functions
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
212
 
Note
With regard to the phase-selective pickup messages, a special behavior is observed in the three-phase voltage 
protection with phase-to-phase variables, because the phase-selective pickup message "Flx01 Pickup Lx" is 
allocated to the respective measured-value channel "Lx". 
Single-phase faults: 
If, for example, voltage V
A
 drops to such degree that voltages V
AB
 and V
CA
 exceed their threshold values, the 
device indicates pickups “Flx01 Pickup A” and “Flx01 Pickup C”, because the undershooting was detected in 
the first and third measured-value channel. 
Two-phase faults: 
If, for example, voltage V
AB
 drops to such degree that its threshold value is reached, the device then indicates 
pickup "Flx01 Pickup A", because the undershooting was detected in the first measured-value channel.