Technical Data
4.3 Inverse-Time Overcurrent Protection 51(N)
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
353
Influencing Variables for Pickup and Dropout
Power supply direct voltage in range 0.8 ≤ V
PS
/V
PSNom
≤ 1.15 1 %
Temperature in range 23.00 °F (-5 °C) ≤ Θ
amb
≤ 131.00 °F (55 °C) 0.5 %/10 K
Frequency in range of 50 Hz to 70 Hz
Frequency in range 0.95 ≤ f/f
Nom
≤ 1.05 1 %
Frequency outside range 0.95 ≤ f/f
Nom
≤ 1.05 Increased
tolerances
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
1%
1%
Transient overreaction during fundamental harmonic measuring procedure for τ > 100 ms
(with full displacement)
<5 %