EasyManua.ls Logo

Siemens SIPROTEC 7SK80 - Page 353

Siemens SIPROTEC 7SK80
490 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
4.3 Inverse-Time Overcurrent Protection 51(N)
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
353
Influencing Variables for Pickup and Dropout
Power supply direct voltage in range 0.8 V
PS
/V
PSNom
1.15 1 %
Temperature in range 23.00 °F (-5 °C) Θ
amb
131.00 °F (55 °C) 0.5 %/10 K
Frequency in range of 50 Hz to 70 Hz
Frequency in range 0.95 f/f
Nom
1.05 1 %
Frequency outside range 0.95 f/f
Nom
1.05 Increased
tolerances
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
1%
1%
Transient overreaction during fundamental harmonic measuring procedure for τ > 100 ms
(with full displacement)
<5 %

Table of Contents

Related product manuals