Appendix
A.3 Connection Examples
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
417
Figure A-17 Transformer connections to three current transformers, cable-type current transformer and
broken delta winding, maximum precision for sensitive ground fault detection
Important: Grounding of the cable shield must be effected at the cable side
For busbar-side grounding of the current transformers, the current polarity of the device is changed via address
0201. This also reverses the polarity of the current input IN/INs. When using a cable-type current transformer,
the connection of k and I at F8 and F7 must be exchanged.