1471 50BF TRIP (50BF TRIP) 50BF BkrFailure OUT * on m LED BO 160 85 2 No
1480 50BF (internal) TRIP (50BF int
TRIP)
50BF BkrFailure OUT * on * LED BO 166 180 2 Yes
1481 50BF (external) TRIP (50BF ext
TRIP)
50BF BkrFailure OUT * on * LED BO 166 181 2 Yes
1503 >BLOCK 49 Overload Protection
(>BLOCK 49 O/L)
49 Th.Overload SP * * * LED BI BO 167 3 1 Yes
1507 >Emergency start of motors
(>EmergencyStart)
49 Th.Overload SP On
Off
**LEDBIBO16771Yes
1511 49 Overload Protection is OFF
(49 O / L OFF)
49 Th.Overload OUT On
Off
* * LED BO 167 11 1 Yes
1512 49 Overload Protection is
BLOCKED (49 O/L BLOCK)
49 Th.Overload OUT On
Off
On
Off
* LED BO 167 12 1 Yes
1513 49 Overload Protection is
ACTIVE (49 O/L ACTIVE)
49 Th.Overload OUT On
Off
* * LED BO 167 13 1 Yes
1515 49 Overload Current Alarm (I
alarm) (49 O/L I Alarm)
49 Th.Overload OUT On
Off
* * LED BO 167 15 1 Yes
1516 49 Overload Alarm! Near
Thermal Trip (49 O/L Θ Alarm)
49 Th.Overload OUT On
Off
* * LED BO 167 16 1 Yes
1517 49 Winding Overload (49 Winding
O/L)
49 Th.Overload OUT On
Off
* * LED BO 167 17 1 Yes
1521 49 Thermal Overload TRIP (49
Th O/L TRIP)
49 Th.Overload OUT * on m LED BO 167 21 2 Yes
1580 >49 Reset of Thermal Overload
Image (>RES 49 Image)
49 Th.Overload SP On
Off
**LEDBIBO
1581 49 Thermal Overload Image reset
(49 Image res.)
49 Th.Overload OUT On
Off
**LEDBO
1704 >BLOCK 50/51 (>BLK 50/51) 50/51 Overcur. SP * * * LED BI BO
1714 >BLOCK 50N/51N (>BLK
50N/51N)
50/51 Overcur. SP * * * LED BI BO
1718 >BLOCK 50-3 (>BLOCK 50-3) 50/51 Overcur. SP * * * LED BI BO 60 144 1 Yes
1719 >BLOCK 50N-3 (>BLOCK 50N-3) 50/51 Overcur. SP * * * LED BI BO 60 145 1 Yes
1721 >BLOCK 50-2 (>BLOCK 50-2) 50/51 Overcur. SP * * * LED BI BO 60 1 1 Yes
1722 >BLOCK 50-1 (>BLOCK 50-1) 50/51 Overcur. SP * * * LED BI BO 60 2 1 Yes
1723 >BLOCK 51 (>BLOCK 51) 50/51 Overcur. SP * * * LED BI BO 60 3 1 Yes
1724 >BLOCK 50N-2 (>BLOCK 50N-2) 50/51 Overcur. SP * * * LED BI BO 60 4 1 Yes
1725 >BLOCK 50N-1 (>BLOCK 50N-1) 50/51 Overcur. SP * * * LED BI BO 60 5 1 Yes
1726 >BLOCK 51N (>BLOCK 51N) 50/51 Overcur. SP * * * LED BI BO 60 6 1 Yes
1730 >BLOCK Cold-Load-Pickup
(>BLOCK CLP)
ColdLoadPickup SP * * * LED BI BO
1731 >BLOCK Cold-Load-Pickup stop
timer (>BLK CLP stpTim)
ColdLoadPickup SP On
Off
* * LED BI BO 60 243 1 Yes
1732 >ACTIVATE Cold-Load-Pickup
(>ACTIVATE CLP)
ColdLoadPickup SP On
Off
**LEDBIBO
1751 50/51 O/C switched OFF (50/51
PH OFF)
50/51 Overcur. OUT On
Off
**LEDBO60211Yes
1752 50/51 O/C is BLOCKED (50/51
PH BLK)
50/51 Overcur. OUT On
Off
On
Off
* LED BO 60 22 1 Yes
1753 50/51 O/C is ACTIVE (50/51 PH
ACT)
50/51 Overcur. OUT On
Off
**LEDBO60231Yes
1756 50N/51N is OFF (50N/51N OFF) 50/51 Overcur. OUT On
Off
**LEDBO60261Yes
1757 50N/51N is BLOCKED (50N/51N
BLK)
50/51 Overcur. OUT On
Off
On
Off
* LED BO 60 27 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation