EasyManuals Logo
Home>Siemens>Protection Device>SIPROTEC 7UT613 series

Siemens SIPROTEC 7UT613 series User Manual

Siemens SIPROTEC 7UT613 series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #196 background imageLoading...
Page #196 background image
2 Functions
196
7UT613/63x Manual
C53000-G1176-C160-2
2.7 Single-Phase Time Overcurrent Protection
The single-phase time overcurrent protection can be assigned to either of the single-
phase measured additional current inputs of the device. This may be a „normal“ input
or a high-sensitivity input. In the latter case, a very sensitive pickup threshold is pos-
sible (smallest setting 3 mA at the current input).
The single-phase time overcurrent protection comprises two definite time delayed
stages which can be combined as desired. If only one stage is required, set the other
to ∞.
Examples for application are high-impedance differential protection or high-sensitivity
tank leakage protection. These applications are covered in the following subsections.
2.7.1 Function Description
The measured current is filtered by numerical algorithms. Due to high sensitivity, a
particularly narrow band filter is used.
For the single-phase I>>-stage, the current measured at the assigned current input is
compared with the setting value 1Phase I>>. Current above the pickup value is de-
tected and annunciated. When the delay time T I>> has expired, tripping command
is issued. The reset value is approximately 95 % of the pickup value for currents above
I
N
. For lower values the dropout ratio is reduced in order to avoid intermittent pickup
on currents near the setting value (e.g. 90 % at 0.2 · I
N
).
When high fault current occurs, the current filter can be bypassed in order to achieve
a very short tripping time. This is automatically done when the instantaneous value of
the current exceeds the set value I>> stage by at least factor 2 · √2 .
For the single-phase I>-stage, the current measured at the assigned current input is
compared with the setting value 1Phase I>. Current above the pickup value is de-
tected and annunciated. When the delay time T I> has expired, the tripping command
is issued. The reset value is approximately 95 % of the pickup value for currents above
I
N
. Lower values require a higher hysteresis in order to avoid intermittent pickup on
currents near the pickup value (e.g. 80 % at 0.1 · I
N
).
Both stages form a two-stage definite time overcurrent protection (figure 2-84).
Figure 2-85 illustrates the logic diagram for the single-phase overcurrent stage

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT613 series and is the answer not in the manual?

Siemens SIPROTEC 7UT613 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT613 series
CategoryProtection Device
LanguageEnglish

Related product manuals