2 Functions
138
7UT613/63x Manual
C53000-G1176-C160-2
2.3 Restricted Earth Fault Protection
The restricted earth fault protection detects earth faults in power transformers, shunt
reactors, neutral earthing transformers/reactors, or rotating machines, the starpoint of
which is led to earth. It is also suitable when a starpoint former is installed within a pro-
tected zone of a non-earthed power transformer. A precondition is that a current trans-
former is installed in the starpoint connection, i.e. between the starpoint and the earth-
ing electrode. The starpoint CT and the phase CTs define the limits of the protected
zone exactly. Restricted earth fault protection is not applicable to busbars.
7UT613/63x provides a second earth fault differential protection. The following func-
tion description refers to the 1st instance (address 13xx). The 2nd instance is set via
addresses 14xx.
2.3.1 Application Examples
Examples are illustrated in the Figures 2-50 to 2-56.
Figure 2-50 Restricted earth fault protection on an earthed transformer winding
Figure 2-51 Restricted earth fault protection on an earthed winding of a single-phase power
transformer

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT613 series and is the answer not in the manual?

Siemens SIPROTEC 7UT613 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT613 series
CategoryProtection Device
LanguageEnglish

Related product manuals