EasyManuals Logo
Home>Siemens>Protection Device>SIPROTEC 7UT613 series

Siemens SIPROTEC 7UT613 series User Manual

Siemens SIPROTEC 7UT613 series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #281 background imageLoading...
Page #281 background image
2.19 Monitoring Functions
281
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-114 Current Symmetry Monitoring
Voltage Symmetry In healthy network operation it can be expected that the voltages are nearly balanced.
If measured voltages are connected to the device, this symmetry is checked in the
device by magnitude comparison. To do this, the phase-to-earth voltages are mea-
sured. The lowest phase-to-earth voltage is set in relation to the highest. An imbalance
is detected when
|U
min
|/|U
max
| < BAL. FACTOR U as long as |U
max
| > BALANCE U-LIMIT
TherebyU
max
is the largest of the three phase-to-phase voltages and U
min
the smallest.
The symmetry factor BAL. FACTOR U is the measure for the asymmetry of the con-
ductor voltages; the limit value BALANCE U-LIMIT is the lower limit of the operating
range of this monitoring (see Figure Voltage Symmetry Monitoring). Both parameters
can be set. The dropout ratio is about 95 %.
This malfunction is reported as „Fail U balance“.
Figure 2-115 Voltage Symmetry Monitoring

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT613 series and is the answer not in the manual?

Siemens SIPROTEC 7UT613 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT613 series
CategoryProtection Device
LanguageEnglish

Related product manuals