EasyManua.ls Logo

Siemens SIPROTEC 7UT613 series - Page 400

Siemens SIPROTEC 7UT613 series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Mounting and Commissioning
400
7UT613/63x Manual
C53000-G1176-C160-2
Amplitude measurement with switched on test current:
Compare the indicated current magnitudes under measurement secondary
operational measured values secondary with the actually flowing values:
This applies for all measuring locations included in the test.
Note: The WEB Monitor provides comfortable read-out possibilities for all mea-
sured values with visualisation using phasor diagrams (Figure 3-27).
If deviations occur that cannot be explained by measuring tolerances, either a con-
nection or the test setup is wrong:
Switch off the test source and the protected object (shut down the generator) and
earth it,
Re-check the assignment or the tested measuring location (Section 2.1.4 under
margin heading „Assignment of 3-phase measuring locations“).
Re-check the settings for the magnitude matching (Subsection 2.1.4 under
margin heading „Current Transformer Data for 3-phase Measuring Locations“).
Re-check the plant connections to the device and the test arrangement and
correct them.
If a substantial zero sequence current 3I0 occurs one or two of the currents of the
corresponding side must have a reversed polarity.
3I0 phase current one or two phase currents are missing;
3I0 double phase current one or two phase currents with reversed polarity.
Repeat test and re-check the current magnitudes.
Figure 3-27 Phasor Diagram of the Secondary Measured Values — Example

Table of Contents

Related product manuals