Engineering and remote access
7.4 SIMATIC STEP 7 in the TIA Portal
Power supply system SITOP PSU8600
182 Manual, 09.2018, A5E36758446-5-76
Buffering The parameters are set here for buffer modules with double-layer
capacitors or UPS modules
Parameterization is only possible if an
appropriate module exists in the system.
• Deactivate the buffer component using a control command.
• Activate the LONGLIFE operating mode (only buffer module
with Double layer capacitors).
• Define the threshold value for the "Sufficient buffer readiness"
message.
• Activate short-time interruption at output 1.
• Time X: Dead time up to the beginning of short time interrup-
tion.
• Time A: Wait time until the short-time interruption.
• Time B: Duration of short-time interruption.
If UPS modules are assigned, then additional parameters can be
defined:
• Time C: Waiting time after client shutdown completed
• Preferred UPS module when the power supply voltage fails
• Define as to whether buffer components are charged before
outputs are activated.
• Define that only one output is activated when starting from a
battery module.
PROFIenergy Here, you activate and configure energy management with
Web interface General Make the following settings:
• Possibility of accessing via a web server (yes/no)
• Automatic logoff when closing the web server (yes/no)
• Permit access only with HTTPS (yes/no)
Automatic up-
date
Make the following settings:
• Activate automatic update (yes/no)
• Time interval for the update
OPC UA
server
OPC UA
Here, activate the OPC UA server.
Unencrypted
access activat-
You have the option of activating unencrypted access to the
OPC UA server. However, this option is not recommended.
OPC UA server
Specify which port should be used.