Engineering and remote access
7.4 SIMATIC STEP 7 in the TIA Portal
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
183
Navigation area
Description
NTP client NTP client
activated
Here, activate the NTP client.
NTP server
address 1 … 4
Enter up to 4 addresses for NTP server.
A detailed description of the individual parameters is provided in Sections "Parameterizing
the basic unit (Page 185)" and "Parameterizing output 1 (Page 191)".
Note
Under "Device configuration > Output 1
n", a note can be saved that informs users
whether parameters for the output can be controlled from a PLC program during the runtime.
The note is saved by activating (selecting) point "The configuration of the output can differ
during runtime because it is controlled remotely". For a download, this information is not
written to the device, it is only saved in
the STEP 7 project file.
Parameters of the expansion modules
For parameterizing the expansion modules, in the area navigation, settings under "Module
configuration > Output 1 n" are relevant.
Navigation area
Description
Module con-
figuration
Output 1 … n Here, make the following settings for the individual outputs:
Switch-on and switch-off output.
Setpoint output voltage
Response threshold of the output current
Define a threshold to issue an alarm.
An alarm is output if this threshold is continually exceeded for
5 ms.
Define the on delay.
Define the operating modes: ELECTRONIC SHUTDOWN or
CONSTANT CURRENT
A detailed description of the individual parameters of the subgroup is provided in Section
"Parameterizing output 1 (Page 191)".
Note
Under "Module configuration > Output 1
n", a note can be saved that informs users that
parameters for the output can be controlled from a PLC program during
the runtime. The
note is saved by activating (selecting) point "The configuration of the output can differ during
runtime because it is controlled remotely". For a download, this information is not written to
the device, it is only saved in the STEP 7 proj
ect file.