Engineering and remote access
7.4 SIMATIC STEP 7 in the TIA Portal
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
189
Define that only output 1 is activated when starting from a battery module
If the SITOP PSU8600 is activated with the energy from a battery module, then only
output 1 is activated. The other outputs are only activated once the supply voltage is
connected/is available.
Output parameters
Outputs are parameterized at the basic units and at the expansion modules in the same
identical way. You can find a list of the parameters in Section "Parameterizing output 1
(Page 191)".
PROFIenergy parameters
Parameter
Value range
Default setting
Enable PROFIenergy on this device Yes/no No
Time to pause
0 - 2147483647
0 ms
Time to operation
0 - 2147483647
0 ms
Minimum dwell time
0 - 2147483647
0 ms
Maximum dwell time
0 - 2147483647
0 ms
Save power consumption
0.000 - 100000.000
0.00 kW
Operate power consumption
0.000 - 100000.000
0.00 kW
Energy consumption required until going into the
energy-saving mode
0.000 - 100000.000 0.00 kWh
Energy consumption required until going into the
operating state
0.000 - 100000.000 0.00 kWh