Engineering and remote access
7.4 SIMATIC STEP 7 in the TIA Portal
Power supply system SITOP PSU8600
190 Manual, 09.2018, A5E36758446-5-76
Note
Response for a PROFIenergy pause:
As soon as the command to start a PROFIenergy pause is issued via PROFINET, the
operating status of t
he outputs cannot be influenced using switch-on or shutdown
commands, which are sent in the REMOTE operating mode during the PROFIenergy pause.
These commands are buffered up to the end of the PROFIenergy pause.
The configuration of the outputs is automat
ically updated as soon as the command to exit
the PROFIenergy pause is issued. All of the switch
-on and shutdown commands that
occurred during the PROFIenergy pause are taken into account.
All other commands are immediately executed, even during a PROFIen
ergy pause.
PROFIenergy output parameters
The outputs are selected by setting a checkmark.
Parameter
Default setting
Outputs that can be switched off for a PROFIenergy pause
None
Web server parameters
Parameter
Value range
Default setting
Activate web server on this module
Yes/no
No
Enable automatic logoff
Yes/no
No
Permit access only with HTTPS
Yes/no
Yes
Enable automatic update
Yes/no
No
Update interval
0 / 5 s / 10 s / 20 s / 30 s / 60 s
10 s