Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
226 Manual, 09.2018, A5E36758446-5-76
Input data SITOP PSU8600
Slot
Subslot
Data
Description
Data size
0 2
Fill byte(s)
-
Unsigned16
Device input voltage [100mV] Input voltage basic unit: rms value of the
SITOP PSU8600 power supply input
voltage.
Unsigned16
Device output current [10mA] System load current power supply sys-
tem: Sum of the actual load currents at all
outputs of the power supply system.
Unsigned16
Device operating state Operating state of the overall power sup-
ply system.
Unsigned8
Buffer ready [0/255] The power supply system is ready for
buffering, and has sufficient buffer readi-
ness (only relevant for systems with
SITOP BUF8600 4 s/10 s).
Unsigned8
Charging state [0-100%] The system charge state as a percent-
age; i.e. the total charge state of all
SITOP BUF8600 4 s/10 s buffer compo-
nents in the power supply system.
Note: If only the SITOP BUF8600
100 ms/300 ms exists in the system, then
this value is always "0%".
Unsigned8
Buffering disabled [0/255] All buffer components of the power sup-
ply system are deactivated via control
command
or
the control contact of a
SITOP BUF8600 4 s/10 s.
Unsigned8
Actual total charging power [024,000] Charging power in steps of 0.01 W
(0 - 240.00 W)
Unsigned16
0 3 Output voltage [10mV] Actual voltage at the output of the power
supply system.
Unsigned16
Output current [10mA] Actual load current at the output of the
power supply system.
Unsigned16
Operation state Operating state at the output of the power
supply system.
Unsigned8
Detailed information about the individual operating states can be found in Section "Operating
states SITOP PSU8600 (Page 234)".