EasyManua.ls Logo

Siemens SITOP PSU8600 - Page 227

Siemens SITOP PSU8600
420 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
227
Input data SITOP CNX8600
6EP4436-8XB00-0CY0 (4x5 A) and 6EP4437-8XB00-0CY0 (4x10 A)
Slot
Subslot
Data
Description
Data size
1-6 1 Module operation state Operating state of the expansion module
SITOP CNX8600.
Unsigned8
2 Channel1 output voltage [10mV] Actual voltage at output 1 of the power
supply system.
Unsigned16
Channel1 output current [10mA] Actual load current at output 1 of the
power supply system.
Unsigned16
Channel1 operation state Operating state at output 1 of the power
supply system
Unsigned8
1-6 3 Channel2 output voltage [10mV] Actual voltage at output 2 of the power
supply system
Unsigned16
Channel2 output current [10mA] Actual load current at output 2 of the
power supply system
Unsigned16
Channel2 operation state Operating state at output 2 of the power
supply system
Unsigned8
1-6 4 Channel3 output voltage [10mV] Actual voltage at output 3 of the power
supply system
Unsigned16
Channel3 output current [10mA] Actual load current at output 3 of the
power supply system
Unsigned16
Channel3 operation state Operating state at output 3 of the power
supply system
Unsigned8
1-6 5 Channel4 output voltage [10mV] Actual voltage at output 4 of the power
supply system.
Unsigned16
Channel4 output current [10mA] Actual load current at output 4 of the
power supply system.
Unsigned16
Channel4 operation state Operating state at output 4 of the power
supply system
Unsigned8
6EP4436-8XB00-0DY0 (8x2.5 A)
Slot
Subslot
Data
Description
Data size
1-6 1 Module operation state Operating state of the expansion module
SITOP CNX8600.
Unsigned8
2 Channel1 output voltage [10mV] Actual voltage at output 1 of the power
supply system.
Unsigned16
Channel1 output current [10mA] Actual load current at output 1 of the
power supply system.
Unsigned16
Channel1 operation state Operating state at output 1 of the power
supply system
Unsigned8
1-6 3 Channel2 output voltage [10mV] Actual voltage at output 2 of the power
supply system
Unsigned16
Channel2 output current [10mA] Actual load current at output 2 of the
power supply system
Unsigned16
Channel2 operation state Operating state at output 2 of the power
supply system
Unsigned8