Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
228 Manual, 09.2018, A5E36758446-5-76
Slot
Subslot
Data
Description
Data size
1-6 4 Channel3 output voltage [10mV] Actual voltage at output 3 of the power
supply system
Unsigned16
Channel3 output current [10mA] Actual load current at output 3 of the
power supply system
Unsigned16
Channel3 operation state Operating state at output 3 of the power
supply system
Unsigned8
1-6 5 Channel4 output voltage [10mV] Actual voltage at output 4 of the power
supply system.
Unsigned16
Channel4 output current [10mA] Actual load current at output 4 of the
power supply system.
Unsigned16
Channel4 operation state Operating state at output 4 of the power
supply system
Unsigned8
1-6 6 Channel5 output voltage [10mV] Actual voltage at output 5 of the power
supply system.
Unsigned16
Channel5 output current [10mA] Actual load current at output 5 of the
power supply system.
Unsigned16
Channel5 operation state Operating state at output 5 of the power
supply system
Unsigned8
1-6 7 Channel6 output voltage [10mV] Actual voltage at output 6 of the power
supply system.
Unsigned16
Channel6 output current [10mA] Actual load current at output 6 of the
power supply system.
Unsigned16
Channel6 operation state Operating state at output 6 of the power
supply system
Unsigned8
1-6 8 Channel7 output voltage [10mV] Actual voltage at output 7 of the power
supply system.
Unsigned16
Channel7 output current [10mA] Actual load current at output 7 of the
power supply system.
Unsigned16
Channel7 operation state Operating state at output 7 of the power
supply system
Unsigned8
1-6 9 Channel8 output voltage [10mV] Actual voltage at output 8 of the power
supply system.
Unsigned16
Channel8 output current [10mA] Actual load current at output 8 of the
power supply system.
Unsigned16
Channel8 operation state Operating state at output 8 of the power
supply system
Unsigned8
Detailed information about the individual operating states can be found in Section "Operating
states SITOP CNX8600 (Page 235)".