Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
243
4 = StartupDelay
Variable
Variable on delay: De-
pending on the parame-
terized delay time,
outputs are activated after
the supply voltage is
Soft Output
Characteristics Output
Soft output characteristic of output 1 of the SITOP PSU8600 is activated. Unsigned8
Ithreshold (0-100%) Prewarning threshold for the actual system power, referred to the rated power
of the power supply system.
Unsigned8
Reset Reset all outputs: Resets the automatic overload shutdown of all outputs. As-
suming that the outputs are not switched off elsewhere, then after the reset,
they are switched on again.
Unsigned8
System overload alarm
Time delay before an alarm is issued after a system overload was detected. Unsigned16
Main power outage
alarm threshold time
Time delay before an alarm is issued after failure of the power supply voltage
(power supply changes into the BUFFER MODE).
Unsigned16
Index 1: Channel1 (reading/writing)
Currently set setpoint of the output voltage.
Ilimit [mA] Response threshold of the output current for an output. When this is exceeded,
the output current is interpreted as having an overload condition and is shut
down with a time delay - or limited.
The response threshold is set in the following steps depending on the maxi-
mum output current:
• Output current 20 A: 20 mA (0.02 A)
• Output current 40 A: 40 mA (0.04 A)
Values that deviate from this grid are rounded off to the next permissible value
Unsigned16
Ithreshold (0-100%) Prewarning threshold of the configured response threshold for the output cur-
rent in %. An alarm is initiated when the actual output current exceeds this
value. Operation is continued without any restrictions. Prewarning is deactivat-
Unsigned8
OutputEnable (0/255) Switch on output Switches the output on or off. A possible automatic shutdown
due to overload or power failure is not taken into account.
Unsigned8
Reset Resets the output: Resets the automatic overload shutdown of an output. As-
suming that the output is not switched off elsewhere, then after the reset, it is
Unsigned8