Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
244 Manual, 09.2018, A5E36758446-5-76
Operation Mode Operating mode: If the
actual load current of an
output exceeds the speci-
fied response threshold
value of the output cur-
rent, then the output can
be switched off according
to a current-time charac-
teristic ("electronic shut-
down"), or the load
current can be limited to
the response threshold
0 = ModeSelect Electronic shutdown: The
output is switched off
when the response
threshold value is ex-
Unsigned8
1 = ModeModular Constant current: When
the response threshold
value is exceeded, the
load current is limited to
the response threshold
until this is fallen below
again.
Startup Delay [ms] On delay Individual delay time for the output, referred to a common starting
point. Only valid for system switch-on behavior "Variable on delay".
Unsigned16
Index 6: Device information (reading)
Index 7: Hardware settings (reading)
Man/remote DipSwitch (0/255) Actual position of the operating selection switch at
the basic unit SITOP PSU8600:
• 0 = MANUAL mode
• 255 = REMOTE mode
Unsigned8
Priority Buffered Channel 1 DipSwitch (0/255) Current switch position for prioritized buffering
(PRIO) of output 1 on the basic unit
Unsigned8
Startup Mode DipSwitch – Combination (0-3) Current switch position for the system startup
characteristics.
• StartupDelayOff = 0
• StartupDelay25ms = 1
• StartupDelay100ms = 2
• StartupDelayLoadOptimized = 3
Unsigned8
Operating Mode DipSwitch (0/255) Actual switch position for the mode of output 4 at
the basic unit SITOP PSU8600:
• 0 = constant current
• 255 = electronic shutdown
Unsigned8