Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
265
Index 32: State information (reading)
Actual Charging Power
Actual charging power Unsigned16
Maximum permitted
charging power
Maximum permitted
charging power
Unsigned8
2 = High (default set-
120 W charging power
Module operation state Operating state 0 = Off UPS module is in the
Unsigned8
1 = Boot UPS module is presently
2 = Default Complete buffer readi-
ness: The energy storage
device of the UPS module
is fully charged (normal
3 = Buffering UPS module is in the
buffer mode: The power
supply system is supplied
4 = ErrorOff Shutdown after error: An
error occurred when op-
erating the UPS module.
The UPS module is not
operational and must be
restarted by switching off
the supply voltage and
5 = ReadyForRestart UPS module is ready to
8 = Disable UPS module is deactivat-
9 = FWUpdate A firmware update is
presently being per-
formed.
The basic unit generates
11=BatteryTest Battery test is being car-
Battery state Operating state of the
connected battery mod-
ules
0 = Off UPS module is in the
Unsigned8
1 = Boot UPS module is presently
booting.