Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
296 Manual, 09.2018, A5E36758446-5-76
Buffer component disabled via control command
Threshold value for sufficient buffer readiness 10 - 90 % 85 %
Short time interruption at output 1 is enabled
Dead time until start of short-time interruption sequence 0 - 3 600 000 000 ms 3 000 ms
Waiting time up to short time interruption
Duration of short time interruption
Waiting time after client shutdown completed
Preferred buffer component if the power supply voltage
fails
• Alternating dis-
charge
• UPS8600[1]
• UPS8600[2]
Alternating
discharge
Preferred charging mode for a system start
Only switch-on one output after starting from the battery