Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
319
Alarm_MD_Systemoverload Boolean Sitop_8600_AlarmType The system load lies about the
nominal maximum value, but still
within the defined overload profile.
The device is still functioning com-
Alarm_MD_SystemConfigReadError Boolean Sitop_8600_AlarmType The system configuration cannot
be read out of the EEProm.
Alarm_MD_SystemParametersCorrupt Boolean Sitop_8600_AlarmType The stored system configuration is
incorrect/corrupt. Deviations from
the expected response can occur if
the device is not operated under
Alarm_MR_ModuleParametersCorrupt Boolean Sitop_8600_AlarmType The stored module configuration is
incorrect/corrupt. The device con-
tinues to operate consistently.
Alarm_MR_MoreCapableModuleDetec-
Boolean Sitop_8600_AlarmType Module with excessive power de-
Alarm_MR_NewModuleDetected Boolean Sitop_8600_AlarmType A new module has been found that
has still not been configured.
Alarm_MR_Output1InterruptionShutdow
Boolean Sitop_8600_AlarmType Shutdown of output 1 is initiated.
Alarm_MR_ShutdownPrimary Boolean Sitop_8600_AlarmType The resonance converter of the
power supply is shut down.
Alarm_MR_Systemoverload Boolean Sitop_8600_AlarmType The system load is above the set
system load alarm threshold.
Alarm_MR_SystemoverloadPeakLoad Boolean Sitop_8600_AlarmType The system load is outside the
defined overload profile (either
because of the magnitude or be-
cause the time was excessively
long). The outputs of the channel
expansions are shut down.
Alarm_MR_SystemParametersCorrupt Boolean Sitop_8600_AlarmType The system configuration is defec-
tive/false. The system can be op-
Alarm_MR_SystemShutdown Boolean Sitop_8600_AlarmType General error. The device is still
functioning as configured and as
Alarm_MR_SystemStateBuffering
Alarm_MR_SystemStateCooledDown Boolean Sitop_8600_AlarmType After a system overload / after a
short-circuit, the device has cooled
down again, and can be reactivat-
ed after switching off the supply
Alarm_MR_SystemStateReadyForRe-
start
Boolean Sitop_8600_AlarmType System can be switched on again
after automatic shutdown due to
impermissible operating condition.
To reactivate the system, it must
be switched-off and switched-on
again - or it must be restarted using