Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
320 Manual, 09.2018, A5E36758446-5-76
Display name
Data type
Definition
Description
Alarm_MR_UnexpectedModuleDetected
Boolean
Sitop_8600_AlarmType
Unexpected module type detected.
Alarm_N_BufferDisabled Boolean Sitop_8600_AlarmType Buffer deactivated.
Alarm_N_ChargingDisabledByCommand Boolean Sitop_8600_AlarmType Loading the buffer component(s)
using the control command deac-
tivated
Alarm_N_RestartAfterSafetyShutdown Boolean Sitop_8600_AlarmType The device has been restarted
after an automatic shutdown.
Alarm_N_SerialnumberDiverge
Boolean
Sitop_8600_AlarmType
Different serial number detected.
Alarm_N_SetpointParametersOutOf
Range
Boolean Sitop_8600_AlarmType A parameter value is outside its
maximum value (e.g. the S7 at-
tempts to set 28.8 V; however, the
module can only provide 28.0 V,
and therefore goes into limiting).
Alarm_N_SoftwareVersionDiverge Boolean Sitop_8600_AlarmType The alarm is displayed in conjunc-
tion with the alarm to replace the
module.
Alarm_N_SystemModeManual Boolean Sitop_8600_AlarmType The device was switched to the
MANUAL mode. Control via the
PLC is now no longer possible.
Alarm_N_SystemStateStartup Boolean Sitop_8600_AlarmType Information that the system will be
started.
Alarm_N_UCMBuffering
Boolean
Sitop_8600_AlarmType
Buffer mode.
Alarm_N_UCMReady
Boolean
Sitop_8600_AlarmType
Ready for buffering.
Alarm_N_ClientShutdownFinished
Boolean
Sitop_8600_AlarmType
Client run down.
Alarm_N_ClientShutdownInitiated Boolean Sitop_8600_AlarmType System has initiated that the client
is run down.
Alarm_MR_BufferingNotPossible
Boolean
Sitop_8600_AlarmType
Buffering not possible.
Alarm_MR_BufferingInsufficientCharging Boolean Sitop_8600_AlarmType Module is not sufficiently charged
in order to be able to buffer.
Alarm_N_BufferingDisabledByCommand
Boolean
Sitop_8600_AlarmType
Buffering remotely deactivated.
Alarm_N_ChargingDisabledByCommand
Boolean
Sitop_8600_AlarmType
Charging remotely deactivated.
Alarm_MR_InputOvervoltage Boolean Sitop_8600_AlarmType An overvoltage condition was de-
tected at the input.
Alarm_MR_InputUndervoltage
Boolean
Sitop_8600_AlarmType
Voltage at the input is too low.
Alarm_MD_ShutdownPrimary Boolean Sitop_8600_AlarmType The resonance converter of the
power supply was shut down.
Alarm_MD_SystemConfigReadError Boolean Sitop_8600_AlarmType The system configuration cannot
be read from the EEPROM.
Variables "ID" and "Severity" are assigned to each alarm.