Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
343
Display name
Data type
Definition
Description
Alarm_MR_BatteryPackDefect Boolean PropertyType The battery voltage inside the
module exhibits an abnormal de-
viation and should be replaced in
order to avoid buffering problems.
Alarm_MR_BatteryParameters
Corrupt
Boolean PropertyType The battery configuration is corrupt.
The battery behavior remains un-
changed, however.
Alarm_MR_BatteryPowerlineDis-
connected
Boolean PropertyType Connection to battery interrupted -
check connection and fuse
Alarm_MR_BatteryTemperature
HighError
Boolean PropertyType Battery temperature is too high and
the battery was shut down for safe-
ty reasons. Buffering is no longer
possible depending on the number
of connected batteries.
Alarm_MR_BatteryTemperature
HighWarning
Boolean PropertyType Battery temperature too high
battery life will be shortened
Alarm_MR_BatteryTemperature
LowError
Boolean PropertyType The battery temperature is too low.
The battery will not operate in this
situation. Buffering is no longer
possible depending on the number
of connected batteries.
Alarm_MR_BatteryTemperature
LowWarning
Boolean PropertyType Battery temperature too low - re-
duced output current
Alarm_MR_FuseBlown
Boolean
PropertyType
Fuse is defective
Alarm_MR_MoreCapableBattery
Detected
Boolean PropertyType A module with excessive power
was detected. Normal operation of
the system is possible.
Alarm_MR_NewBatteryDetected
Boolean
PropertyType
New battery detected
Alarm_MR_UnexpectedBatteryDe-
tected
Boolean PropertyType Unexpected module type detected.
Alarm_MR_UnknownBatteryDe-
tected
Boolean PropertyType Unexpected module type detected.
Alarm_N_BatteryLifetimeCounter
Reseted
Boolean PropertyType After the battery was successfully
replaced, the determination of the
battery lifetime was reset and then
restarted.
Alarm_N_EndOfServiceLifeWar-
ning
Boolean PropertyType It is recommended to replace the
battery because the battery lifetime
has reached its calculated end and
restricted buffer readiness is prob-
able.
Alarm_N_SerialnumberDiverge
Boolean
PropertyType
Different serial number detected
Alarm_N_SoftwareVersionDiverge
Boolean
PropertyType
Different firmware version detected
ParameterSet
/
All variables of the SITOP UPS8600 battery module are listed together under the
"ParameterSet" node.