SubDevices
The parameters for the battery modules are listed under the "SubDevices" nodes.
SITOP BAT8600 battery modules
ActualState
Display name
Data type
Definition
Description
ModuleOperatingState Enumeration MultiStateDiscrete-
Type
Battery status
ModuleStateOfHealth Integer AnalogItemType State of health of the battery mo-
dule
ModuleCapacity
Integer
AnalogItemType
Capacity of the battery module
ModuleTemperature
Integer
AnalogItemType
Battery temperature
ModuleOperatingHours
Integer
AnalogItemType
Total operating time of the batteries
ModuleStateLed Object Sitop_8600_LedType Actual state of the LED display
"O.K."
Alarm
Display name
Data type
Definition
Description
Alarm_MR_BatteryCommunication
Disconnected
Boolean PropertyType Communication to the battery is
interrupted. Buffering is still possi-
ble, the battery charge level has
been reduced to a minimum how-
ever.
Alarm_MD_BatteryDefect Boolean PropertyType Battery defective - neither buffer
nor charging operation is possible
Alarm_MD_BatteryParameters
Corrupt
Boolean PropertyType The battery configuration is corrupt.
Battery behavior may deviate.
Alarm_MD_BatteryTemperature
HighError
Boolean PropertyType Battery temperature is too high and
the battery was shut down for safe-
ty reasons. Buffering is no longer
possible depending on the number
of connected batteries.
Alarm_MD_BatteryTemperature
LowError
Boolean PropertyType The battery temperature is too low.
The battery will not operate in this
situation. Buffering is no longer
possible depending on the number
of connected batteries.
Alarm_MD_IncompatibleBatteryDe-
tected
Boolean PropertyType The battery is a type that is not
compatible with the configuration.
The battery cannot be commis-
sioned.
Alarm_MD_LessCapableBattery
Detected
Boolean PropertyType A module with reduced power was
detected. Deviating system beha-
vior may be possible.
Alarm_MR_BatteryDeepDischarge Boolean PropertyType Battery is deep discharged - no
buffering possible.