Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
341
Alarm_N_SafetyBufferingExtension
Running
Boolean PropertyType The multiple buffer event over-
stress protection was activated,
because three buffer events oc-
Alarm_N_SerialnumberDiverge
Different serial number detected
Alarm_N_SoftwareDownload Boolean PropertyType The firmware download to the
system has been completed suc-
cessfully. A system reset is re-
quired to run the firmware update.
Alarm_N_SoftwareVersionDiverge
Different firmware version detected
Alarm_N_SOHTestRunning Boolean PropertyType Battery 'State of Health' tests (SoH)
See Section "Lock (Page 323)".
StartCapacityTracingTest Method - Battery 'State of Health' tests (SoH)
StopCapacityTracingTest Method - Battery 'State of Health' tests (SoH)
/
All variables of the SITOP UPS8600 UPS module are listed together under the
"ParameterSet" node.
Parameters not described otherwise, in alphabetical order:
ModuleBatteryTestIntervalSetpoint Enumeration MultiStateDiscrete-
Type
Interval in which the automatic
battery test is executed (0 = never,
1, …, 24 = every 1, …,24 hours)
ModuleBufferTimerSetpoint Integer AnalogItemType Set time until the buffer timer ex-
ModuleBufferTimerEnableSetpoint
The buffer time is activated
ModuleMaximumChargingpo-
werSetpoint
Enumeration MultiStateDiscrete-
Type
Maximum permissible charging
power (0 W = off, 60 W = low,