Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
340 Manual, 09.2018, A5E36758446-5-76
Display name
Data type
Definition
Description
MR_BatteryDisconnectedSubslot1 Boolean PropertyType The connection to the battery is
lost either due to disconnection
(power or communication) or re-
moval of the battery. (Sub-slot 1)
MR_BatteryDisconnectedSubslot2 Boolean PropertyType The connection to the battery is
lost either due to disconnection
(power or communication) or re-
moval of the battery. (Sub-slot 2)
MR_BatteryDisconnectedSubslot3 Boolean PropertyType The connection to the battery is
lost either due to disconnection
(power or communication) or re-
moval of the battery. (Sub-slot 3)
MR_BatteryDisconnectedSubslot4 Boolean PropertyType The connection to the battery is
lost either due to disconnection
(power or communication) or re-
moval of the battery. (Sub-slot 4)
MR_BatteryDisconnectedSubslot5 Boolean PropertyType The connection to the battery is
lost either due to disconnection
(power or communication) or re-
moval of the battery. (Sub-slot 5)
Alarm_MR_BatteryPowerlineDis-
connected
Boolean PropertyType The power connection to the bat-
tery is interrupted. The battery can
no longer be buffered or charged.
Alarm_MR_BufferStateBuffering Boolean PropertyType The power supply system is sup-
plied via the buffer components.
Alarm_MR_ExceedingBatteryCount Boolean PropertyType More than 5 batteries are connect-
ed. Connect a maximum of 5 bat-
teries to the Energy Storage Link.
Alarm_MR_General Boolean PropertyType General error occurred. Device
behavior remains consistent, how-
ever.
Alarm_MR_ModuleParameters
Corrupt
Boolean PropertyType Stored module configuration is
corrupt. Module behavior remains
consistent, however.
Alarm_MR_MoreCapableModule
Detected
Boolean PropertyType A module with excessive power
was detected. Normal operation of
the system is possible.
Alarm_MR_NewModuleDetected
Boolean
PropertyType
New unconfigured module detected
Alarm_MR_UnexpectedModuleDe-
tected
Boolean PropertyType Unexpected module type detected.
Alarm_N_BufferingDisabledBy
Contact
Boolean PropertyType Buffer component disabled via
control contact
Alarm_N_BufferStateFull Boolean PropertyType Ready for buffering. Energy stor-
age fully charged.
Alarm_N_BufferStateNotFull Boolean PropertyType Limited buffer capacity. Energy
storage is not fully charged.
Alarm_N_BufferTimerExceeded Boolean PropertyType The configured maximum buffer
time has expired. The output is
switched off.