Troubleshooting
8.3 Alarm list web server
Power supply system SITOP PSU8600
370 Manual, 09.2018, A5E36758446-5-76
48 F Critical error A critical error occurred. All outputs of the power supply
(module/system) have been switched off.
49 MD Critical error General critical error occurred. The device may therefore
behave inconsistently.
50 MR General error. General error occurred. Device behavior remains consistent,
51 F Performing firmware update. Performing firmware update. Read/write access is currently
52 F Stored module configuration cor-
Stored module configuration is corrupt. The module cannot
53 MD Stored module configuration cor-
Stored module configuration is corrupt. Deviating module
behavior may be possible.
54 MR Stored module configuration cor-
Stored module configuration is corrupt. Module behavior
remains consistent, however.
55 F Hardware failure A hardware failure has occurred. All outputs of the power
supply system have been switched off.
Different firmware version detected
Different firmware version detected
57 MR New unconfigured module detect-
New unconfigured module detected.
Different serial number detected
Different serial number detected
59 MR Module with excessive power de-
A module with excessive power was detected. Normal oper-
ation of the system is possible.
60 MR Unexpected module type detected. Unexpected module type detected.
61 MD Module with reduced power de-
A module with reduced power was detected. Deviating sys-
tem behavior may be possible.
62 F Incompatible module detected. The module has a module type that is incompatible with the
configuration. The module cannot be commissioned.
Unexpected empty slot detected.
Unexpected empty slot detected.
75 N Parameter out of permissible value
range.
A control command is attempting to set a value outside the
value range that the hardware module can implement. The
value is automatically limited to the minimum or maximum
permitted value for the module.
76 N Parameter out of permissible value
range.
A control command is attempting to set a value outside the
value range that the hardware module can implement. The
value is automatically limited to the minimum or maximum
permitted value for the module.
77 N Parameter out of permissible value
range.
A control command is attempting to set a value outside the
value range that the hardware module can implement. The
value is automatically limited to the minimum or maximum
permitted value for the module.
78 N Parameter out of permissible value
range.
A control command is attempting to set a value outside the
value range that the hardware module can implement. The
value is automatically limited to the minimum or maximum
permitted value for the module.
79 N Parameter out of permissible value
range.
A control command is attempting to set a value outside the
value range that the hardware module can implement. The
value is automatically limited to the minimum or maximum
permitted value for the module.