Description, device design, dimension drawing
2.8 Display elements
Power supply system SITOP PSU8600
50 Manual, 09.2018, A5E36758446-5-76
States of the individual LEDs
Table 2- 11 LED "O.K."
Signaling
Off
Device is OFF or is powering up (booting)
Green
Normal operation
Red
ERROR OFF: Module automatically shut down due to overtemperature basic
unit or phase imbalance
Shutdown due to system overload (limited for 60 s, followed by automatic
return to normal operation)
Fault in the module or communication error to the basic unit
Flashing red (0.25/0.25)
Module ready for the automatic ERROR OFF shutdown to be reset or after
a firmware update has been completed, by switching off the supply voltage
and switching it on again (power OFF/ON)
Device shut down due to firmware update of another system component
Incorrect hardware configuration (REMOTE mode)
Yellow
Power failure, buffer mode active
Alternating, green/red
(0.25/0.25)
Firmware being updated.