51
Table 2- 12 LED "ON/OFF/RST"
Signaling
Off
Device is OFF or is powering up (booting)
or
ERROR OFF shutdown
or
NEC Class 2 shutdown
or
Incorrect hardware configuration (REMOTE operating mode)
or
Firmware being updated/completed
Green
Normal operation, output current < response threshold value
Flashing green (0.25/0.25) Overload at the output: Output current 101 - 150 % of the response threshold
up to 149 %: operation permissible for 5 s, 150 %: operation permissible for
200 ms
Flashing green (1/1)
For overload, the output current is limited to the response threshold value
(CONSTANT CURRENT mode)
Red Output automatically switched off due to:
Overload exceeding the permissible time range (ELECTRONIC SHUTDOWN
mode)
Output 1 prioritized for buffer mode
System overload
Overtemperature of the output (in pairs)
Flashing red (0.25/0.25)
After automatic shutdown due to overload, system overload or overtemperature,
output is ready for reset by pressing the button, reset signal or control command
Flashing red (1/1)
Output switched off via control command (REMOTE mode)
Yellow
Output manually switched off using the button at the device