Description, device design, dimension drawing
2.8 Display elements
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
51
Table 2- 12 LED "ON/OFF/RST" ②
Off
• Device is OFF or is powering up (booting)
or
• ERROR OFF shutdown
or
• NEC Class 2 shutdown
or
• Incorrect hardware configuration (REMOTE operating mode)
or
• Firmware being updated/completed
Normal operation, output current < response threshold value
Flashing green (0.25/0.25) Overload at the output: Output current 101 - 150 % of the response threshold
up to 149 %: operation permissible for 5 s, 150 %: operation permissible for
Flashing green (1/1)
For overload, the output current is limited to the response threshold value
Red Output automatically switched off due to:
• Overload exceeding the permissible time range (ELECTRONIC SHUTDOWN
mode)
• Output 1 prioritized for buffer mode
• System overload
• Overtemperature of the output (in pairs)
Flashing red (0.25/0.25)
After automatic shutdown due to overload, system overload or overtemperature,
output is ready for reset by pressing the button, reset signal or control command
Output switched off via control command (REMOTE mode)
Output manually switched off using the button at the device