Operator control at the device
3.3 Overload shutdown and carrying out a reset
Power supply system SITOP PSU8600
86 Manual, 09.2018, A5E36758446-5-76
Carrying out a reset with the button at the device
The output can be reset using the button. This resets the electronic shutdown of the output,
caused by an overload condition.
Button (illuminated with an LED)
The initial situation is an electronic shutdown as a result of an overload condition. This is
signaled using LED "ON/OFF/RST" in button
①:
Lit red Electric shutdown due to an overload.
Wait time until a reset is possible: 5 seconds.
Flashes red Output ready for a reset
Press the button to switch-on the output again.
The reset was carried out, the output was switched-on again.
1. After an electronic shutdown, wait 5 seconds (LED "ON/OFF/RST" of the output is lit red).
2. Press the button of the output, which is ready for a reset (LED "ON/OFF/RST" of the
output flashes red).
Electronic shutdown is reset, and the output has been switched-on again (LED
"ON/OFF/RST" of the output is lit green).
Note
If, after a reset, the cause of the overload is still present, then the output is again
automatically switched off according to the shutdown characteristics.
To prevent a new shutdown, before carrying out a RESET, remove the cause of the
overload.