Operator control at the device
3.3 Overload shutdown and carrying out a reset
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
87
Remote reset via terminal RST
The reset can be alternatively carried out using a remote reset signal. The non-isolated 24 V
input (referred to terminal "0V" of the device) at terminal "RST" can be used. A reset is
carried out for an input level of > 15 V for at least 100 ms.
● Connect a voltage of > 15 V for at least 100 ms to terminal "RST".
The reset is carried out.
-on delay of the outputs is defined when switching on, then this is not taken into
account for a reset initiated using a remote reset signal (function only available when using a
CNX8600 expansion module).
Note
The rising edge of the reset signal is evaluated. This means for an additional reset signal,
the voltage level must first dro
p down to below 13 V.