A.9.13 Oil table settings
Table A-140 Oil table settings (only hydrocarbon applications)
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
750 Unsigned / 2 Command Command to update
LiquIdent lookup table
0
0: Command done /
not executing
1: Transfer
information to oil table
2: Read information
from oil table
3: Perform sanity
check
4: Store table to flash
5: Erase flash
6: Reload latest valid
table from flash
7: Sort oil table in
ascending order by
LiquIdent
Read /
write
751 Unsigned / 2 Command sta‐
tus
Status of last per‐
formed Command
0
0: STATUS_OK -
command executed
successfully
1:
SANITY_CHECK_FA
ILED - sanity check
failed during
command execution
2: MEMORY_FULL -
out of flash storage
space. Erase needed
3:
MEMORY_TIMEOUT
- indicates timeout
during flash write/
erase operation
4:
MEMORY_LOAD_FA
ILED - indicates error
with loading data
from flash
Read
only
752 Unsigned / 2 Index Index affected by Com‐
mand
Write (ID 1)
Read (ID 2)
1 1 - 30 Read /
write
Modbus communication
A.9 Modbus holding registers tables
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD 333