Serial no. Transmitter serial number
System revisions System revision numbers; firmware (FW) and hardware (HW)
Power Supply Power supply
Material/Version Transmitter housing material and style (compact/remote)
Conduit / cable en‐
tries
Type of conduit / cable entries
Enclosure IP / Am‐
bient temp.
Degree of protection / Ambient temperature
Year of Manufac‐
ture
Manufacturing year
More detailed manufacturing date information is given in the serial num‐
ber (see sensor identification nameplate above)
SW function Software function
Ch1 Communication interface on channel 1
Ch2
Ch3
Ch4
Ch5
Ch6
Input/output setup of channels 2 to 4, if ordered
Channels 5 and 6 always available
WEEE symbol, see Disposal (Page 86)
Consult the Operating Instructions
C✓ / QR-code C-tick logo and product-specific QR-code
Figure 5-1 Transmitter nameplate example
See also
Approvals (Page 129)
Installation in hazardous areas (Page 19)
5.4 Integrating the FST030 with Modbus system
This chapter provides information on how to integrate the device in a point-to-point or multidrop
Modbus RTU network in non-hazardous or hazardous areas. Many details of network design
are beyond the scope of these operating instructions. The points below provide an overview of
the major design criteria. For further details contact Siemens.
If the device is integrated in a hazardous area, two flameproof conduit seals per device must be
installed; one at the device in the hazardous area and one in the non-hazardous area, see
System configuration (Page 35).
Connecting
5.4 Integrating the FST030 with Modbus system
SITRANS FST030 (Modbus)
34 Operating Instructions, 08/2018, A5E37367739-AD